MODEL 2434

  • Least affected by external stray magnetic field.
  • 20mA AC max. in proximity to a 15mm-dia conductor carrying 100A AC
  • Frequency Selector Switch to eliminate the effect of harmonics.
  • Resolution 0.1mA.

CE

  • φ28
  • MAX100A
  • Filter
AC A (50/60Hz) 400mA/4/100A ±2%rdg±4dgt
AC A (WIDE) 400mA/4/100A
±2%rdg±4dgt [50/60Hz]
±3%rdg±5dgt [40 – 400Hz]
Conductor size Ø28mm max.
Frequency response 40 – 400Hz
Effect of external stray magnetic field φ15mm 100A 20mA AC max.
Safety Standard IEC 61010-1 CAT III 300V IEC 61010-2-032
Power source R03 (AAA) (1.5V) × 2
Dimensions 169(L) × 75(W) × 40(D)mm
Weight 220g approx.
Included Accessories 9097 Carrying Case
R03 × 2
Instruction Manual
Optional Accessories 8008 (Multi-Tran)*

Accessories/ Optional Accessories /Related Products


Other Products

203

200

MODEL 2433R

MODEL 2433

MODEL 2432

MODEL 2431

KEW 2413R

KEW 2413F

MODEL 2412

MODEL 2300R

KEW 2056R

KEW 2055