KEW 6010B

  • Continuity:20/200Ω 200mA Test Current
  • Insulation: 500/1000V, 20/200MΩ 1mA Rated Test Current
  • Loop Impedance:20/2000Ω 15mA Test Current at 2000Ω (No RCD Trip)
  • RCD:10/30/100/300/500mA x1/2, x1, Fast Trip(40ms), DC, Auto Ramp
  • Test of a large kind of RCD's:Standard, Selective, AC and A(DC sensitive breakers)
  • Uc(Contact Voltage): 100V
  • Designed to IEC 61010-1, IEC 61557
  • Data Memory:300 measured results
  • The stored data can be transferred to PC via Optical Adaptor Model 8212-USB or 8212-RS232C.

CE

Continuity Testing
Measuring Range 20/200Ω (Auto-Ranging)
Open Circuit Voltage > 6V
Short Circuit Current > 200mA
Accuracy ±(3%rdg + 3dgt)
Insulation Resistance Testing
Measuring Range 20/200MΩ (Auto-Ranging)
Test Voltage 500/1000V
Open Circuit Voltage +20% – 0%
Rated Current > 1mA
Accuracy ± (3%rdg + 3dgt)
Loop Impedance Testing
Impedance Range 20/2000Ω
Rated Voltage 230V + 10% – 15%(50Hz)
Normal Test Current 20Ω:25A/10ms
2000Ω:15mA/350ms max.
Accuracy ±(3%rdg + 8dgt)
RCD Testing
Test Current
(Test Current Duration)
x1/2, x1 10, 30, 100, 300, 500mA (2000ms)
Fast 150mA (50ms)
DC 10, 30, 100, 300mA (2000ms), 500mA (200ms)
Auto Ramp Goes up by 10% from 20% to 110% of IΔn. 300ms×10
Rated Voltage 230V + 10% – 15% 50Hz
Accuracy Test Current x1/2: -8%-2%
x1, FAST: +2%+8%
DC: ±10%
Auto Ramp: ±4%
Trip Time ±(1%rdg + 3dgt)
Uc Testing
Measuring Range 100V
Rated Voltage 230V + 10% – 15% (50Hz)
Test Current 5mA at IΔn=10mA
15mA at IΔn=30/100mA
150mA at IΔn=300/500mA
Accuracy +5%+15%rdg, ±8dgt

Accessories/ Optional Accessories /Related Products


Other Products

KEW 6024PV

MODEL 6018

KEW 6016