KEW 5410

  • Measurement of RCD trip time  Conducting testing of rated residual non-operating currents at × 1/2 Range, measuring RCD trip time at × 1 and × 5 Ranges.
  • Measurement of trip out current  Measuring trip out current by varying current automatically.
  • Remote Test  Enabling a user to hold the Test Leads with his both hands by locking the Test Button. Measurement will automatically start when the main voltage is detected.
  • Voltage Measurement  Carrying out a constant measurement of voltage in the stand-by mode at each Range.
  • Auto-detection of Contact voltage Detecting the voltage to earth of Earth electrodes or Protective conductors during RCD test – when applying test currents – at measurement using EARTH in order to prevent electrical shocks caused by the damaged earth. Measurement will be ceased at AC50V or more.
  • Dust- and Water-proof Dust- and Water-proof construction (designed to IEC 60529 IP54).
  • Backlight Facilitating working at dimly illuminated locations.

CE

Measurement of RCD trip time – Measurement of trip out current

Range× 5× 1× 1/2AUTO RAMP(mA)
Rated Voltage100V±10%
200V-10%~+32%
400V±10%
50/60Hz
Test current15/30/50/100mA15/30/50/100/200/500mA15/30/50/100/200/500mA
Measuring rangeTesting time
0ms~200ms
Testing time
0ms~2000ms
Testing time
0ms~2000ms
40% – 110% of lΔn
(goes up by 5%)
Testing time
300ms × 15steps
Accuracy
(Trip Time)
1%rdg±3dgt1%rdg±3dgt1%rdg±3dgtTest Current at each step
-4%~+4%
Accuracy
(Trip Time)
+2%~+8%dgt+2%~+8%dgt-8%~-2%dgt

Voltage Measurement

Measuring range80V~450V 50/60Hz
Accuracy2%rdg±4dgt
Applicable standardsIEC 61010-1 Pollution degree2 CAT III 300V / CAT II 400V
IEC 61010-031
IEC 61557-1, 6
IEC 60529 (IP54)
Display1999 counts (3 1/2digits), Large LCD
Operating temperature & humidity range0ºC – 40ºC, relative humidity 85% (no condensation)
Storage temperature & humidity range-20ºC – 60ºC, relative humidity 85% (no condensation)
Insulation resistance50MΩ or more / 1000V (between electrical circuit and enclosure)
Sleep Function(1)Automatically enters Sleep mode in 3 minutes after the last switch operation (current consumption 75µA). This function doesn’t work at voltage measurements. To exit from the Sleep mode, set the Function switch to OFF position once, and re-set it to the Range at which a measurement to be conducted.
(2) Backlight turns off in 1 minute after it lights up.
Power sourceDC 12V / Size AA battery R6 (SUM-3) × 8 pcs.
Dimensions167(L)×186(W)×89(D)mm
WeightApprox. 965g (including batteries)
Possible number of Measurements1200 times or more
(measure every 30 seconds at ×1/2 Range, lΔn=100mA)
Included Accessories7128A (Test leads)
7129A (Test lead with alligator clip)
8017 (Long pin) × 2
Cord case, 9121 (Shoulder strap), Instruction manual,
Size AA battery R6 (SUM-3) × 8pcs.

(*) Only the RCD type G (without trip out time-delay) can be tested at Auto Ramp Test,
type S (time-delay) cannot be tested.